Which rule governs and who it binds

The national technical reference is the Basic Document on Fire Safety (DB-SI) of the Technical Building Code, approved by Royal Decree 314/2006 and amended several times since. A wedding, banquet or conference room is, for its purposes, a public assembly use ("Pública Concurrencia"). Section SI 3 deals with the evacuation of occupants and SI 4 with protection installations.

The DB-SI binds the building: it is met in the project, checked when the licence is granted and recorded in it. On top of that come the regional rules on public entertainment and leisure activities, municipal bylaws and, depending on the activity and the capacity, the obligation to have a self-protection plan. Premises with a licence from before the Technical Building Code are governed by what their licence established.

This article summarises what the Spanish national rule says so that whoever sets up a room understands why exits and aisles are the way they are. It is not legal advice and does not replace the project: the values that bind your venue are those of its licence, and any change to exits or routes needs a competent technician.

How many exits a room needs

Table 3.1 of section SI 3 allows a single exit from a space only when the occupancy does not exceed 100 people and the length of the evacuation routes to that exit does not exceed 25 m, with some exceptions that do not affect an ordinary room. The limit drops to 50 people if you have to climb more than 2 m to get out, as happens in some basements and cellars.

Above 100 people at least two exits are needed. The route to at least one of them can then be up to 50 m, but the initial stretch, up to the point where you can already choose between two different paths, cannot exceed 25 m. These lengths can be increased by 25% when the sector is protected by an automatic extinguishing system.

The occupancy used for this calculation is not the number of guests on Saturday, but the room's design occupancy, which comes from applying the DB-SI's own densities to its area. The relationship between that figure and the capacity of a banquet has its own guide.

How wide doors and aisles must be

Table 4.1 gives a single formula for doors, passages and aisles: A ≥ P / 200, where A is the width in metres and P the number of people expected to pass through that point. Two hundred people call for 1.00 m; three hundred, 1.50 m. There are also minimums: 0.80 m for doors and passages and 1.00 m for aisles, whatever the result of the division.

Door leaves have their own limit: none can measure less than 0.60 m or more than 1.23 m. That is why the exits of a large room have two leaves, and why a double door with one leaf fixed, bolted or hidden behind a curtain is not the exit shown in the project.

The point that surprises most is the blocked-exit assumption. When a room must have more than one exit, the calculation does not comfortably spread people between them all: it assumes that one of them, the one that does most harm, is out of use, and requires the others to absorb all the occupants. That is the reason no exit is dispensable, even if day to day only the main one is used.

Doors: how they open and what is in front of them

Doors intended as a floor or building exit, and those intended to evacuate more than 50 people, have to be hinged with a vertical pivot axis. Their fastening either does not operate while there is activity, or it opens easily and quickly from the side the people come from, without a key and without operating more than one mechanism. An emergency exit locked with a key or a padlock during an event breaches that condition.

Exit doors intended for the passage of more than 100 people, or for more than 50 occupants of the space they serve, must open in the direction of evacuation. In practice, those of any banquet room.

For the set-up this translates into two zones that have to be empty: the inside, up to the door, and the arc the leaf sweeps when opening, together with the space it opens onto. A cart of stacked chairs in the outside corridor puts an exit out of action just as a table placed inside does.

A 20 × 15 m room, with the rule's numbers

To see how the formulas work, an illustrative example; it is not a project. A room of 300 m² usable, calculated as a multi-purpose room at 1 m² per person: occupancy of 300.

Exits: with 300 people, more than one. If it has two and one is assumed blocked, all 300 people go through the other: A ≥ 300 / 200 = 1.50 m. Each exit needs at least 1.50 m of clear width, which leads to double doors, for example with 0.80 m leaves. If it has three identical exits and one is blocked, the other two share 150 people each: 150 / 200 = 0.75 m, which rises to the minimum of 0.80 m.

Aisles: the one leading 300 people to an exit needs 1.50 m; the one leading 150, the minimum of 1.00 m.

Routes: the room's diagonal measures 25 m, so in the empty room, with two exits on opposite walls, any point is well below 50 m. But the route is measured along where you can walk. With banquet-table rows 10 m long, someone in the middle of a row has to follow it to the end before turning towards the door, and that detour counts.

On the wedding day there are 130 guests seated, less than half the design occupancy. The doors are still the same and still all have to be usable: the room was authorised with that set of exits, not with part of it.

What falls to the set-up team

Whoever draws the plan for a wedding does not size exits, but is the one who decides whether they are still fit for purpose. These are the working rules that keep the set-up within what the project foresaw.

  • Exits are drawn before tables. First mark all the exit doors and the aisle that has to be left to each one; the tables go in what remains.
  • In front of each exit, a clear strip at least as wide as the door, and better wider. In MisePlan, a door marked as an emergency exit reserves by default an aisle 1.80 m wide towards the interior, adjustable on each door, and the plan warns if a table intrudes on it. It is a working rule, not the legal figure: the width required is the one in the project.
  • The swing of doors is a no-go zone, inside and out.
  • The main routes between tables towards the exits are treated as aisles, not as service aisles: straight, with no cable ramps or loose rugs, and at full width even when the chairs are occupied.
  • Nothing added at the last minute goes in an exit: photocall, signing table, candy bar, mobile bar, speakers, improvised cloakroom.
  • Decoration does not cover signs or equipment. Exit signs must be visible from any point and extinguishers must stay in view and within reach.
  • Hanging fabrics count. The DB-SI requires curtains, drapes and other suspended textiles in public assembly premises to have a reaction-to-fire classification (Class 1 under the UNE-EN 13773 standard). Ask for the certificate from whoever installs the fabric ceilings or the drapery.

Rows of chairs in theatre-style set-ups

For rooms with fixed seats, such as cinemas and auditoriums, table 4.1 regulates the gap between rows. In rows with access to an aisle at both ends, the clear gap must be at least 30 cm up to 14 seats, and 1.25 cm more for each additional seat. In rows with access at one end only, 30 cm up to 7 seats and 2.5 cm more for each additional seat, with a maximum of 12. And at most every 25 rows there has to be a cross aisle of at least 1.20 m.

That rule is written for fixed seats. For loose chairs in a room it is the reference used, and it is where the figures the trade works with come from: blocks of up to 14 chairs between two aisles, or of 7 against a wall. The 30 cm gap is measured between the most protruding part of one row and that of the next; with a row of chairs every 0.95 m, about 50 cm is left, which complies with room to spare.

Aisles between blocks are sized like any evacuation aisle: A ≥ P / 200, with a minimum of 1.00 m. Some regional and municipal rules add conditions for non-fixed chairs, such as having them linked together in rows; you need to check the one that applies to the venue.

Gardens, terraces and marquees

Outdoor areas are treated more loosely, but they are not outside the rule. Table 4.1 sizes their passages and aisles with A ≥ P / 600, and table 3.1 allows longer routes, up to 75 m with more than one exit, in outdoor spaces where the fire risk is irrelevant. If the garden's evacuation goes through the inside of the building, the interior elements are generally sized as interiors.

A closed marquee stops being open air. It is a space with an occupancy, exits and routes, and its fabric enclosures have their own fire-behaviour requirements: the DB-SI asks for level T2 under the UNE-EN 15619 standard or class C-s2,d0. It is also a temporary installation, which normally requires its technical documentation and, depending on the municipality, authorisation. Ask the installer for the certificates and confirm the procedure with the town council before selling the set-up.

Check before opening the doors

Ten minutes with the plan in hand, when the set-up is finished and before the first guest comes in.

  • Walk to each exit from inside: reach the door without moving anything, open it fully and check there is nothing on the other side either.
  • Check that no exit is closed with a key, chain or bolt.
  • Look from the centre of the room and from the corners: at least one exit sign must be visible.
  • Locate the extinguishers and, if there are any, the fire hose points. If something covers them, move what covers them.
  • Follow the sound, lighting and photo booth cables: none crosses an exit aisle unprotected.
  • Compare with the plan. If the real set-up has drifted, correct the room, not the plan.
  • Brief the team: the floor manager, waiters and suppliers need to know where the exits are and that they are not blocked during the event, not even to unload.